Technical Documentation

Latent & Sensible,
separate type Air Handling Unit

Sensible and latent heat separation air conditioning systems use separate air handling unit​ for treating latent heat and sensible heat, making it possible to provide air conditioning ​without installing a separate air conditioner.​

Dual Coil Air Handling unit

Separating sensible and latent loads improves comfort during partial loads.​

Features

  • The sensible load and latent load are each handled by two coils. ​

Control example

  • The control valve (MV1) adjusts the amount of water passing through the sensible heat treatment coil so that the return air temperature or room temperature is set.​​
  • The control valve (MV2) adjusts the amount of water passing through the latent heat treatment coil so that the return air temperature or room temperature is set.​​

Psychrometric chart movement​

Coil to Coil reheat type Air Handling unit​

By recovering sensible heat from outside air, no heat source is required for reheating after dehumidification, improving energy efficiency.​​

Features

  • Since outside air is used as a reheat source, no heat source is required.​​
  • Heat is circulated between the pre-cooling coil, which pre-cools (PC) the outside air, and the reheat (RH) coil.​

Control example

  • Depending on the return air temperature or room temperature, the circulation pump (P1) is started to reheat.​​​
  • The control valve (MV1) adjusts the amount of water passing through the cooling coil so that the return air humidity or room humidity reaches the set value.​​

Psychrometric chart movement​