Korean Journal of Air-Conditioning and Refrigeration Engineering (설비공학논문집)
- Volume 26 Issue 5
- /
- Pages.199-205
- /
- 2014
- /
- 1229-6422(pISSN)
- /
- 2465-7611(eISSN)
DOI QR Code
IEA ECBCS Annex 54 Economic Assessment Study of a Fuel Cell Integrated Ground Source Heat Pump Microgeneration System
연료전지 지열히트펌프 마이크로제너레이션 IEA ECBCS Annex 54 경제성 평가 연구
- Na, Sun-Ik (Renewable Energy Engineering, University of Science and Technology) ;
- Kang, Eun-Chul (Renewable Energy Engineering, University of Science and Technology) ;
- Lee, Euy-Joon (Energy Efficiency Department, Korea Institute of Energy Research)
- Received : 2013年11月22日
- Accepted : 2014年03月12日
- Published : 2014年05月10日
Abstract
The integration of FC (Fuel Cell) and GSHP (Ground Source Heat Pump) hybrid system could produce a synergistic advantage in thermal and electric way. This study intends to analyse the economical aspect of a FC integrated GSHP hybrid system compared to the conventional system which is consisted with a boiler and a chiller. Based on the hourly simulation, the study indicated that GSHP system and FC+GSHP hybrid system could reduce the energy consumption on a building. The method of the economic assessment has been based on IEA ECBCS Annex 54 Subtask C SPB(Simple Payback) method. The SPB was calculated using the economic balanced year of the alternative system over the conventional (reference) system. The SPB of the alternative systems (GSHP and FC+GSHP) with 50% initial incentive was 4.06 and 26.73 year respectively while the SPB without initial incentive of systems was 10.71 and 57.76 year.
Keywords
- Ground Source Heat Pump;
- Fuel Cell;
- Simple Payback;
- Economic Assessment;
- Renewable Portfolio Standard
- 지열 히트펌프;
- 연료전지;
- 투자환수기간;
- 경제성 평가;
- 신재생에너지공급의무화제도;
References
- Rosato, A., Sibilio, S., and Ciampi, G., 2013, Energy environmental and economic dynamic performance assessment of different micro-cogeneration systems in a residential application, Applied Thermal Engineering, Vol. 59, pp. 599-617. https://doi.org/10.1016/j.applthermaleng.2013年06月02日2
- Entchev, E., Yang, L., Ghorab, M., and Lee, E. J., 2013, Fuel cell-Ground source heat pump simulation study, Canmet ENERGY report, pp. 1-17.
- Entchev, E., Yang, L., Ghorab, M., and Lee, E. J., 2013, Simulation of hybrid renewable microgeneration systems in load sharing applications, Energy, Vol. 50, pp. 252-261. https://doi.org/10.1016/j.energy.2012年11月04日6
- ASHRAE, 2007, Methods of testing for rating combination space heating and water heating appliances, ANSI/ASHRAE 124-2007.
- ASHRAE, 2007, Energy standard for buildings except low-rise residential buildings, ANSI/ASHRAE/IESNA Standard 90.1-2007.
- Tzscheutschler, P., 2013, Policy instruments for microgeneration and related energy technologies in Germany, ECBCS IEA Annex 54 report.
- Hawkes, A. D. and Tzscheutschler, P., 2013, Impact of support mechanisms on microgeneration performance in OECD countries, ECBCS IEA Annex 54 report.
- Good Boiler web site, www.1688-0479.com.
- Danawa web site, www.danawa.com.
- Renewable Energy Sources Unit Price Announcement, 2011, New and renewable energy centre of Korea Energy Management Corporation(KEMCO).
- Korea Electric Power Corporation(KEPCO) web site, cyber.kepco.co.kr.
- Korea Gas Corporation(KOGAS) web stie, www.ko gas.or.kr.
Cited by
- Recent Progress in Air-Conditioning and Refrigeration Research: A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2014 vol.27, pp.7, 2015, https://doi.org/10.6110/KJACR.2015277.380